Wouldn’t start.
I installed a new solenoid starter. Took me a total of 20 minutes. Started right up.
Parts Used:
Solenoid-Starter
  • Bruce from CARNATION, WA
  • Difficulty Level:
    Really Easy
  • Total Repair Time:
    30 - 60 mins
10 of 21 people found this instruction helpful.
Was this instruction helpful to you?
Thank you for voting!
No voltage on secondary side of transformer. Confirmed with meter that transformer windings had infinite resistance.
1. Turn the generator selector switch to "OFF"
2. Remove the 240 volt fuses in the automatic transfer switch to remove power to the transformer.
3. Remove the outside cover from the front of the generator, on the motor end.
4. Remove the 3 screws from the panel covering the controls.
5. Label or make note of which terminals the 4 wires on the transformer go to and disconnect from transformer.
6. Using 9/32 nutdriver, remove the two transformer mounting nuts and lock washers.
7. Remove old transformer from studs and install new one. Reinstall nuts and lock washers.
8. Reconnect the 4 transformer wires.
9. Reinstall the control panel cover and the generator housing end cover.
10. Reinstall the fuses in the automatic transfer switch.
11. Put the generator selector switch back in "Automatic"
Parts Used:
Transformer
  • Laron from GRAND RAPIDS, MI
  • Difficulty Level:
    Easy
  • Total Repair Time:
    15 - 30 mins
  • Tools:
    Nutdriver, Screw drivers
3 of 3 people found this instruction helpful.
Was this instruction helpful to you?
Thank you for voting!